CommercialVertical Turbine

18CMFL Mixed Flow Repair

CPS-Pumps Repair Capabilities

This is a quick Blog detailing a repair of a pump from the field using the CPS-Pumps CMF mixed flow product line and existing customer supplied parts.

This pump is used in a cooling tower application and uses flanged column with an existing flanged discharge head.  This simple repair shows the flexibility that clients have with CPS-Pumps when it comes to repairing product from the field.  This pump is using a 18CMFL single stage mixed flow bowl assembly.  CPS-Pumps provided new flanged 16″ column with weld-in column spiders for shaft support.  These weld-in spiders have a cutlass rubber bearing insert that can be replaced when the need arises.

CMF Flow & Pressure Characteristics

Flows To:  40,000 GPM (11,350 m³/hr)
Heads To:  150+ Feet (31+ m)
Temperatures To:  200ºF (92ºC)
Speed Ranges:  445 RPM To 1800 RPM

Size Range

8″ (200 mm) – 36″ (900 mm)

The discharge head is an existing fabricated steel head that was sand blasted with new primer and finish coat applied.  The existing stuffing box was also re-built by inserting a new bearing and packing supplied by CPS-Pumps.  The top shaft was engineered to terminate at a certain spot in the head and this dimension was matched for easy re-installation in the field.

Keep in mind that re-bowling is yet another option for the entire vertical turbine (CVT), axial flow (CAF) and mixed flow (CMF) product lines.  This option makes for a quick and easy replacement of competitor product.

For additional information or engineering support on these or any other CPS-Pump products please contact CPS-Pumps at the support link below.

support@cps-pumps.com

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.